Usage: | Crossing Tower, Tension Tower, Angle Tower, Terminal Tower, Transposition Tower, Branching Tower, According to Client′s Technical Specification |
---|---|
Conductor Circuit: | as Per Clients |
Certification: | ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Temperature (ºC) | Wind speed (m/s) | Ice thickness (mm) |
Max. temperature | 40 | 0 | 0 |
Mini. temperature | -40 | 0 | 0 |
Ice thickness | -5 | 10 | 10 |
Basic wind speed | -5 | 27 | 0 |
Installation condition | -15 | 10 | 0 |
Annual temperature | 5 | 0 | 0 |
Lightning overvoltage | 15 | 10 | 0 |
Operation overvoltage | 5 | 15 | 0 |
Hot-line work | 15 | 10 |
Item |
Conductor | OPGW | |
JL/G1A-500/35 | JLB20A-170 | ||
construction |
AL | 45×3.76 | |
Steel(Al wrap steel ) | 7×2.51 | 19×3.4 | |
Cross-section (mm2) |
Al | 500.00 | 43.13 |
Steel | 34.60 | 129.37 | |
Total | 535.00 | 172.5 | |
Diameter | 30.11 | 17.01 | |
Length mass (kg/km) | 1650.2 | 1152.0 | |
Elastic module (MPa) | 63000 | 147200 | |
coefficient of linear expansion (1/ºC) | 20.9×10-6 | 13.0×10-6 | |
Rated broken (N) | 119410 | 203380 |
Tower type |
Nominal Height Scope (mm) |
Horizontal span (m) |
Vertical Span (m) |
Angle º |
Nominal height tower weight Kg |
10A1-JC1 | 42 | 550 | 800 | 0~20 | 93551 |
Power voltage |
800KV |
Conductor type |
6×JL/ G3A-900/40 |
Max. operation Tension force (KN/phase) |
463.729 | Un-balance Stress value(%) |
10 |
OPGW Type |
JLB20A-150 | Max. operation Tension force (KN/pc) |
59.523 | Un-balance Stress value(%) |
20 |
Item |
Horizontal span (m) |
Vertical Span (m) |
Representative Span (m) |
Angle º |
Height (m) |
KV |
data | 800 | 1000 | 400 | 0~2 | 57 | 0.65 |
Site condition |
Normal operation condition | Accident condition | Installation condition |
Non-uniform Ice condition |
||||||
Basic wind speed | Ice | Mini. temperature |
Non- broken |
broken | ||||||
Climate condition (t/v/b) |
-5/30/0 | -5/10/10 | -15/0/0 | -5/0/10 | -5/0/10 | -5/10/0 | -5/10/10 | |||
Horizontal loading | conductor | 148504 | 25877 | 0 | 0 | 0 | 13167 | 25877 | ||
Insulator Power fitting |
7644 | 600 | 0 | 0 | 0 | 500 | 600 | |||
OPGW | 13633 | 3937 | 0 | 0 | 0 | 1050 | 3937 | |||
Vertical loading |
conductor | 198980 | 273717 | 165817 | 273717 | 273717 | 165817 | 250887 | ||
Insulator Power fitting |
13729 | 23536 | 13729 | 23536 | 23536 | 13729 | 27334 | |||
OPGW | 14561 | 31731 | 11359 | 31731 | 31731 | 11359 | 27334 | |||
Climate condition (t/v/b) |
-5/30/0 | -5/10/10 | -15/0/0 | -5/0/10 | -5/0/10 | -5/10/0 | -5/10/10 | |||
Stress force | conductor | One side | --- | --- | --- | --- | --- | 406827 | --- | |
The other side | --- | --- | --- | --- | --- | 406827 | --- | |||
Stress differences | 0 | 0 | 0 | 0 | 92746 | --- | 46373 | |||
OPGW | One side | --- | --- | --- | --- | --- | 55539 | --- | ||
The other side | --- | --- | --- | --- | --- | 55539 | --- | |||
Stress differences | 0 | 0 | 0 | 0 | 59523 | ---- | 59523 | |||
Nominal Height (m) |
Foundation distance (mm) | Anchor bolt | |||
Front distance |
Side distance |
Type and quantity | Distance /radius (mm) | Material | |
39 | 8750 | 8750 | 4×M64 | 370 | Chinese type 35 steel |
42 | 9410 | 9410 | |||
45 | 10070 | 10070 | |||
48 | 10730 | 10730 | |||
51 | 11390 | 11390 | |||
54 | 12050 | 12050 | |||
57 | 12710 | 12710 | 4×M68 | 390 | |
60 | 13370 | 13370 | |||
63 | 14030 | 14030 | |||
66 | 14690 | 14690 | |||
69 | 15350 | 15350 | |||
72 | 16000 | 16000 | |||
75 | 16660 | 16660 |
Nominal Height (m) |
Tx | Ty | T | Nx | Ny | N |
39 | 193 | 180 | 1532 | 244 | 210 | 1861 |
42 | 196 | 183 | 1556 | 248 | 215 | 1900 |
45 | 199 | 186 | 1576 | 251 | 219 | 1935 |
48 | 202 | 189 | 1598 | 255 | 224 | 1971 |
51 | 204 | 181 | 1615 | 258 | 229 | 2005 |
54 | 207 | 194 | 1633 | 262 | 233 | 2040 |
57 | 209 | 196 | 1646 | 266 | 238 | 2075 |
60 | 238 | 222 | 1842 | 298 | 266 | 2285 |
63 | 242 | 225 | 1864 | 303 | 271 | 2323 |
66 | 244 | 227 | 1886 | 306 | 275 | 2357 |
69 | 251 | 233 | 1927 | 317 | 287 | 2451 |
72 | 252 | 234 | 1923 | 317 | 286 | 2442 |
75 | 257 | 239 | 1960 | 327 | 297 | 2534 |
Steel material | Anti-push, bending and press strength (N/mm2) | Anti-shear strength (N/mm2) |
|
Grade | Thickness or diameter (mm) | ||
Q235 Steel |
≤16 | 215 | 125 |
>16~40 | 205 | 120 | |
>40~60 | 200 | 115 | |
>60~100 | 190 | 110 | |
Q345 Steel |
≤16 | 310 | 180 |
>16~35 | 295 | 170 | |
>35~50 | 265 | 155 | |
>50~100 | 250 | 145 | |
Q420 Steel |
≤16 | 380 | 220 |
>16~35 | 360 | 210 | |
>35~50 | 340 | 195 | |
>50~100 | 325 | 185 | |
Q460 Steel |
≤16 | 415 | 240 |
>16~35 | 395 | 230 | |
>35~50 | 380 | 220 | |
>50~100 | 360 | 210 |
Item | Grade | Anti-push strength (N/mm2) | Anti-shear strength (N/mm2) |
Fastener for towers |
4.8 | 200 | 170 |
5.8 | 240 | 210 | |
6.8 | 300 | 240 | |
8.8 | 400 | 300 | |
Anchor bolts |
Q235 | 160 | / |
Chinese 35 steel | 190 | / | |
Chinese 45 steel | 215 | / |
No | Code | DESCRIPTION |
1 | GB/T2694-2003 | Power Transmission line Steel tower - Technical requirements for manufacturing |
2 | JGJ81-2002 | Technical specification for welding for steel structure of building |
3 | GB9787-88 | Measuring and allowable tolerance for hot-rolled equal angle |
4 | GB709-88 | Measuring and allowable tolerance for hot-rolled plate and strip |
5 | GB/T699-1999 | Quality Carbon Structural Steel |
6 | GB/T1591-1994 | Low alloy high strength structural Steel |
7 | GB700-88 | Carbon Structural Steel |
8 | GB222-84 | Method of sampling steel for determination of chemical composition and permissible variations |
9 | GB/T228-2002 | Method for Tensile testing of metals |
10 | GB/T232-1999 | Method for Bending test of metals |
11 | GB/T5117-1995 | Carbon Welding Rod |
12 | GB/T5118-1995 | Low Alloy Welding Rod |
13 | GB/T8220-1995 | Welding wires for gas shielding arc welding of carbon and low alloy steels |
14 | GB/T10045-2001 | Carbon steel flux cored electrodes for arc welding |
15 | JB/T7949-1999 | Weld outer dimensions for steel construction |
16 | GB50205-2001 | Test Standard for Acceptance of Steel Structure |
17 | GB/T470-1997 | Zinc Ingot |
18 | GB3098.1-2000 | Mechanical properties of fasteners-Part 1:Bolts, screws and studs |
19 | GB3098.2-2000 | Mechanical properties of fasteners-Part2: Nuts, and thread |
20 | GB3098.3-2000 | Mechanical properties of fasteners-Part3: Fastening screw |
21 | GB/T5780-2000 | Helical Bolts Grade C |
22 | GB/T41-2000 | Helical Nuts Grade C |
23 | GB/T90-2002 | Flat Washer Grade C |
24 | GB/T13912-2002 | Metal Coating, Technical Requirement and Test Method for Hot-dip galvanized Metal Parts |
Standard | Description |
ASTM A6/A6M | Standard specification for general requirements for rolled structural steel bars, plates, and sheet piling. |
ASTM - 6 | - General Requirements for delivery of Rolled Steel Plates, Shapes, sheet Piling Bars for structural used |
ASTM A36/A36-M-97a | Standard specification for Carbon structural steel |
ASTM A123 / A123M-02 | Standard specification for Zinc (Hot-Dip Galvanized) Coatings on iron and steel products |
ASTM A143 / A143M-03 | Standard Practise for Safeguarding Against Embitterment of Hot-Dip Galvanized Structural Steel Products and Procedure for Detecting Embitterment |
ASTM A153/ A153M-05 | Standard specification for zinc coating (Hot-Dip) on iron and steel hardware |
ASTM A - 194 | - Grade for bolt |
ASTM A239 | Standard practice for locating the thinnest spot in a zinc (Galvanized) Coating on Iron or Steel Articles |
ASTM A242 | Standard specification for High-Strength Low-Alloy Structural steel |
ASTM A307 | Standard Specification for Carbon Steel Bolts and Studs, 60000 PSI Tensile strength |
ASTM A370-06 | Standard Test Methods and Definitions for Mechanical Testing of Steel Products |
ASTM A325 | Standard Specification for structural bolts, steel, Heat treated 120/105 ksi minimum tensile strength |
ASTM A-325 or A-354 | - Galvanized hexagonal head of connection bolt |
ASTM A325-97 | Standard Specification for High-strength Bolts for structural steel Joints |
ASTM A384 / A384M-02 | Standard Practise for Safeguarding Against Warpage and Distortion During Hot-Dip Galvanizing of Steel Assemblies. |
ASTM A394-93 | Standard Specification for steel Transmission Tower, Bolts, Zinc Coated and Bare |
ASTMA - 563 | - Class and size of nuts |
ASTMA - 572 | - Chemical composition of steel |
ASTM A572/A572-97c | Standard specification for High-Strength Low-Alloy Columbium-Vanadium Structural steel |
ASTMA - 615 | - The anchor bolt material |
ASTM A673 / A673M-07 | Standard Specification for Sampling Procedure for Impact Testing of Structural Steel |
ASTM B201 | Standard practice for testing Chromatic coating on Zinc and Cadmium surfaces |
ASTM E94-93 | Standard Guide for Radiographic Testing |
ASTM E 709-95 | Standard Guide for Magnetic Particle Examination |
ASCE Manual 72 | - Load testing a simple structure |
ASCE 10-97 | Standard Design of latticed steel transmission structures |
AWS D1.1 | American Welding Society D1,1/D1,1M structural Welding code- Steel |
ANSI B-182-2 | Bolts, nuts and washers dimensions |