| Usage: | Tension Tower, Angle Tower |
|---|---|
| Conductor Circuit: | Double Circuit |
| Certification: | ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| voltage grade | 35kV | conductor code | LGJ-240/30 | Conductor Maximum operation tension forces(N) | 28732 | Conductor unbanlance tension forces take value(%) |
| earth wiretype | GJ-50 | earth wire Maximum operation tension forces(N) | 18360 | earth wire unbanlance tension forces take value(%) |
| Design span/angle Kvvalue | level span (m) |
vertical span(m) | representative span(m) | angle (°) |
calculated height(m) | Span coefficient Kvvalue |
| 300 | 450 | 150/300 | 0-20 | 24 |
| climate condition(t/v/b) | Normal working case | accidentant condition | Installationcondition | |||||
| Max. wind speed | Ice | Mini.temperature | not broken | broken | ||||
| -5/25/0 | -5/10/10 | -20/0/0 | -/0/0 | -/0/0 | -10/10/0 | |||
| horizontal loading | conductor | 5496/5482 | 5267/5507 | 4708/3936 | 3350/3232 | 3492 | 5886/5162 | |
| insulator andpower fitting | ||||||||
| jump string | 94 | 23 | 15 | |||||
| earth wire | 3501/3592 | 3491/3544 | 3028/2940 | 2609/2592 | 2526 | 3154/3071 | ||
| vertical loading | conductor | 4206/1975 | 6569/3364 | 4491/1983 | 3817/2014 | 3817/1252 | 4949/1958 | |
| insulator andpower fitting | ||||||||
| jump string | 300 | 380 | 300 | 300 | 300 | 300 | ||
| earth wire | 1430/594 | 3454/1364 | 2224/594 | 2017/609 | 2017/308 | 2225/594 | ||
| tension forces | conductor | one side | 23447 | 26923 | 26702 | 19807 | 31948 | |
| otherside | 23366 | 28295 | 22323 | 25572 | ||||
| tension force differences | ||||||||
| earth wire | one side | 16097 | 17599 | 17172 | 14328 | 17184 | ||
| otherside | 16605 | 17910 | 16672 | 16712 | ||||
| tension force differences | ||||||||
| Nominal height (m) |
tower foundation distance(mm) | anchor bolt tower foundation distance(mm) | anchor boltspecification | ||
| Fronttower foundation distance | Lateral sidetower foundation distance | Fronttower foundation distance | Lateral sidetower foundation distance | ||
| 9 | 2700 | 2700 | 200 | 200 | 4×M27 |
| 12 | 3150 | 3150 | 200 | 200 | 4×M27 |
| 15 | 3610 | 3610 | 200 | 200 | 4×M27 |
| 18 | 4060 | 4060 | 200 | 200 | 4×M27 |
| 14 | 4510 | 4510 | 200 | 200 | 4×M27 |
| 24 | 4960 | 4960 | 200 | 200 | 4XM27 |
| Nominal height(m) | Tmax | Tx | Ty | Nmax | Nx | Ny |
| 9 | 144.85 | 17.46 | 11.9 | 161.68 | 18.55 | 13.27 |
| 12 | 160.05 | 17.81 | 12.89 | 177.73 | 18.99 | 21.31 |
| 15 | 170.95 | 18.58 | 13.59 | 192.09 | 20.04 | 15.26 |
| 18 | 180.83 | 18.84 | 14.25 | 203.05 | 20.4 | 15.99 |
| 14 | 188.01 | 19.44 | 14.72 | 143.52 | 21.24 | 16.69 |
| 24 | 195.17 | 19.68 | 15.2 | 222.05 | 21.59 | 17.27 |
| Nominal height(m) | 9 | 12 | 15 | 18 | 21 | 24 |
| Tower weight(kg) | 1728 | 2103 | 2597 | 3032 | 3471 | 3991 |
| No | Code | DESCRIPTION |
| 1 | GB/T2694-2003 | Power Transmission line Steel tower - Technical requirements for manufacturing |
| 2 | JGJ81-2002 | Technical specification for welding for steel structure of building |
| 3 | GB9787-88 | Measuring and allowable tolerance for hot-rolled equal angle |
| 4 | GB709-88 | Measuring and allowable tolerance for hot-rolled plate and strip |
| 5 | GB/T699-1999 | Quality Carbon Structural Steel |
| 6 | GB/T1591-1994 | Low alloy high strength structural Steel |
| 7 | GB700-88 | Carbon Structural Steel |
| 8 | GB222-84 | Method of sampling steel for determination of chemical composition and permissible variations |
| 9 | GB/T228-2002 | Method for Tensile testing of metals |
| 10 | GB/T232-1999 | Method for Bending test of metals |
| 11 | GB/T5117-1995 | Carbon Welding Rod |
| 12 | GB/T5118-1995 | Low Alloy Welding Rod |
| 13 | GB/T8110-1995 | Welding wires for gas shielding arc welding of carbon and low alloy steels |
| 14 | GB/T10045-2001 | Carbon steel flux cored electrodes for arc welding |
| 15 | JB/T7949-1999 | Weld outer dimensions for steel construction |
| 16 | GB50205-2001 | Test Standard for Acceptance of Steel Structure |
| 17 | GB/T470-1997 | Zinc Ingot |
| 18 | GB3098.1-2000 | Mechanical properties of fasteners-Part 1:Bolts, screws and studs |
| 19 | GB3098.2-2000 | Mechanical properties of fasteners-Part2: Nuts, and thread |
| 20 | GB3098.3-2000 | Mechanical properties of fasteners-Part3: Fastening screw |
| 21 | GB/T5780-2000 | Helical Bolts Grade C |
| 22 | GB/T41-2000 | Helical Nuts Grade C |
| 23 | GB/T90-2002 | Flat Washer Grade C |
| 24 | GB/T13912-2002 | Metal Coating, Technical Requirement and Test Method for Hot-dip galvanized Metal Parts |
| Standard | Description |
| ASTM A6/A6M | Standard specification for general requirements for rolled structural steel bars, plates, and sheet piling. |
| ASTM - 6 | - General Requirements for delivery of Rolled Steel Plates, Shapes, sheet Piling Bars for structural used |
| ASTM A36/A36-M-97a | Standard specification for Carbon structural steel |
| ASTM A123 / A123M-02 | Standard specification for Zinc (Hot-Dip Galvanized) Coatings on iron and steel products |
| ASTM A143 / A143M-03 | Standard Practise for Safeguarding Against Embitterment of Hot-Dip Galvanized Structural Steel Products and Procedure for Detecting Embitterment |
| ASTM A153/ A153M-05 | Standard specification for zinc coating (Hot-Dip) on iron and steel hardware |
| ASTM A - 194 | - Grade for bolt |
| ASTM A239 | Standard practice for locating the thinnest spot in a zinc (Galvanized) Coating on Iron or Steel Articles |
| ASTM A242 | Standard specification for High-Strength Low-Alloy Structural steel |
| ASTM A907 | Standard Specification for Carbon Steel Bolts and Studs, 60000 PSI Tensile strength |
| ASTM A370-06 | Standard Test Methods and Definitions for Mechanical Testing of Steel Products |
| ASTM A325 | Standard Specification for structural bolts, steel, Heat treated 120/105 ksi minimum tensile strength |
| ASTM A-325 or A-354 | - Galvanized hexagonal head of connection bolt |
| ASTM A325-97 | Standard Specification for High-strength Bolts for structural steel Joints |
| ASTM A384 / A384M-02 | Standard Practise for Safeguarding Against Warpage and Distortion During Hot-Dip Galvanizing of Steel Assemblies. |
| ASTM A394-93 | Standard Specification for steel Transmission tower, Bolts, Zinc Coated and Bare |
| ASTMA - 563 | - Class and size of nuts |
| ASTMA - 572 | - Chemical composition of steel |
| ASTM A572/A572-97c | Standard specification for High-Strength Low-Alloy Columbium-Vanadium Structural steel |
| ASTMA - 615 | - The anchor bolt material |
| ASTM A673 / A673M-07 | Standard Specification for Sampling Procedure for Impact Testing of Structural Steel |
| ASTM B201 | Standard practice for testing Chromatic coating on Zinc and Cadmium surfaces |
| ASTM E94-93 | Standard Guide for Radiographic Testing |
| ASTM E 709-95 | Standard Guide for Magnetic Particle Examination |
| ASCE Manual 72 | - Load testing a simple structure |
| ASCE 10-97 | Standard Design of latticed steel transmission structures |
| AWS D1.1 | American Welding Society D1,1/D1,1M structural Welding code- Steel |
| ANSI B-182-2 | Bolts, nuts and washers dimensions |