Usage: | Crossing Tower, Tension Tower, Angle Tower, Terminal Tower, Transposition Tower, Branching Tower, According to Client′s Technical Specification |
---|---|
Conductor Circuit: | Multi Circuit |
Certification: | ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Temperature (ºC) | Wind speed (m/s) | Ice thickness (mm) |
Max. temperature | 40 | 0 | 0 |
Mini. temperature | -20 | 0 | 0 |
Ice thickness | -5 | 10 | 5/10 |
Basic wind speed | 0 | 32 | 0 |
Installation condition | -5 | 10 | 0 |
Annual temperature | 15 | 0 | 0 |
Lightning overvoltage | 15 | 15 | 0 |
Operation overvoltage | 15 | 18 | 0 |
Hot-line work | 15 | 10 | 0 |
Item |
Conductor | OPGW | |
JGJ-630/45 | LBGJ-150-40AC | ||
construction |
AL | 45/4.2 | 19/3.15 |
Steel(Al wrap steel ) | 7/2.8 | 148.07 | |
Cross-section (mm2) | 666.55 | 15.75 | |
Diameter | 33.60 | 0.6967 | |
Length mass (kg/km) | 2.06 | 90602 | |
Rated broken (N) | 148700 | ||
Elastic module (MPa) | 63000 | 103600 | |
coefficient of linear expansion (1/ºC) | 20.9×10-6 | 15.5×10-6 |
Tower type |
Nominal Height Scope (mm) |
Horizontal span (m) |
Vertical Span (m) |
Angle º |
Nominal height tower weight Kg |
500KV 5-5GB-SZ1 | 450 | 450 | 550 | 30-48 | 42 |
Power voltage |
500KV 5-5GB-SZ1 |
Conductor type |
4×JGJ-630/45 | Max. operation Tension force (KN/phase) | 56506 | Un-balance Stress value(%) | 20 |
OPGW Type |
LBGJ-150-40AC | Max. operation Tension force (KN/pc) |
288296 | Un-balance Stress value(%) | 100 |
Item |
Horizontal span (m) |
Vertical Span (m) |
Representative Span (m) |
Angle º |
Height (m) |
KV |
data | 450 | 450 | 550 | 30-48 | 42 | 0.8 |
Site condition |
Normal operation condition | Non-uniform Ice condition |
Broken | Installation condition |
|||||
Basic wind speed | Ice | Mini. temperature |
|||||||
Climate condition (t/v/b) |
0/32/0 | -5/10/5 | -20/0/0 | -5/0/5 | -5/0/5 | -5/10/0 | |||
Horizontal loading | conductor | 45960 | 7924 | 0 | 0 | 0 | 7049 | ||
Insulator Power fitting |
2400 | 266 | 0 | 0 | 0 | 359 | |||
Jump & string | --- | --- | --- | --- | --- | --- | |||
OPGW | 8744 | 2324 | 0 | 0 | 0 | 953 | |||
Vertical loading |
conductor | 48886 | 61838 | 48886 | 61838 | 61838 | 48886 | ||
Insulator Power fitting |
10963 | 11774 | 10963 | 11774 | 11774 | 10963 | |||
Jump & string | --- | --- | --- | --- | --- | --- | |||
OPGW | 8744 | 2324 | 0 | 0 | 0 | 953 | |||
Climate condition (t/v/b) |
0/32/0 | -5/10/5 | -20/0/0 | -5/0/5 | -5/0/5 | -5/10/0 | |||
Stress force | conductor | One side | 196488 | 186040 | 160344 | --- | --- | 168361 | |
The other side | 196488 | 486040 | 160344 | --- | --- | 168364 | |||
Stress differences | 0 | 0 | 0 | 0 | 56506 | 0 | |||
OPGW | One side | 27667 | 31705 | 212115 | --- | --- | 21456 | ||
The other side | 27667 | 31705 | 21215 | --- | --- | 21456 | |||
Stress differences | 0 | 0 | 0 | 0 | 34181 | 0 | |||
Nominal Height (m) |
Foundation distance (mm) | Anchor bolt | |||
Front distance |
Side distance |
Type and quantity | Distance /radius (mm) | Material | |
30 | 11948 | 11948 | 8×M56 |
854 | Chinese type 45 steel |
33 | 12707 | 12707 | |||
36 | 13466 | 13466 | |||
39 | 14224 | 14224 | |||
42 | 14983 | 14983 | |||
45 | 15741 | 15741 | |||
48 | 16500 | 16500 |
Nominal Height (m) |
Tx | Ty | T | Nx | Ny | N |
30 | 2107.23 | 456.11 | 413.13 | 3840.17 | 554.94 | 511.95 |
33 | 3150.74 | 460.35 | 419.40 | 3892.05 | 558.49 | 517.23 |
36 | 3192.14 | 464.97 | 425.15 | 3944.52 | 563.52 | 523.32 |
39 | 3213.34 | 476.68 | 435.77 | 4000.22 | 569.52 | 528.60 |
42 | 3250.38 | 478.62 | 439.09 | 4046.21 | 574.58 | 535.04 |
45 | 3285.24 | 480.25 | 442.43 | 4088.97 | 578.62 | 540.46 |
48 | 3317.72 | 482.66 | 445.74 | 4130.88 | 582.56 | 545.64 |
Steel material | Anti-push, bending and press strength (N/mm2) | Anti-shear strength (N/mm2) |
|
Grade | Thickness or diameter (mm) | ||
Q235 Steel |
≤16 | 215 | 125 |
>16~40 | 205 | 120 | |
>40~60 | 200 | 115 | |
>60~100 | 190 | 110 | |
Q345 Steel |
≤16 | 310 | 180 |
>16~35 | 295 | 170 | |
>35~50 | 265 | 155 | |
>50~100 | 250 | 145 | |
Q420 Steel |
≤16 | 380 | 220 |
>16~35 | 360 | 210 | |
>35~50 | 340 | 195 | |
>50~100 | 325 | 185 | |
Q460 Steel |
≤16 | 415 | 240 |
>16~35 | 395 | 230 | |
>35~50 | 380 | 220 | |
>50~100 | 360 | 210 |
Item | Grade | Anti-push strength (N/mm2) | Anti-shear strength (N/mm2) |
Fastener for towers |
4.8 | 200 | 170 |
5.8 | 240 | 210 | |
6.8 | 300 | 240 | |
8.8 | 400 | 300 | |
Anchor bolts |
Q235 | 160 | / |
Chinese 35 steel | 190 | / | |
Chinese 45 steel | 215 | / |
No | Code | DESCRIPTION |
1 | GB/T2694-2003 | Power Transmission line Steel tower - Technical requirements for manufacturing |
2 | JGJ81-2002 | Technical specification for welding for steel structure of building |
3 | GB9787-88 | Measuring and allowable tolerance for hot-rolled equal angle |
4 | GB709-88 | Measuring and allowable tolerance for hot-rolled plate and strip |
5 | GB/T699-1999 | Quality Carbon Structural Steel |
6 | GB/T1591-1994 | Low alloy high strength structural Steel |
7 | GB700-88 | Carbon Structural Steel |
8 | GB222-84 | Method of sampling steel for determination of chemical composition and permissible variations |
9 | GB/T228-2002 | Method for Tensile testing of metals |
10 | GB/T232-1999 | Method for Bending test of metals |
11 | GB/T5117-1995 | Carbon Welding Rod |
12 | GB/T5118-1995 | Low Alloy Welding Rod |
13 | GB/T8220-1995 | Welding wires for gas shielding arc welding of carbon and low alloy steels |
14 | GB/T10045-2001 | Carbon steel flux cored electrodes for arc welding |
15 | JB/T7949-1999 | Weld outer dimensions for steel construction |
16 | GB50205-2001 | Test Standard for Acceptance of Steel Structure |
17 | GB/T470-1997 | Zinc Ingot |
18 | GB3098.1-2000 | Mechanical properties of fasteners-Part 1:Bolts, screws and studs |
19 | GB3098.2-2000 | Mechanical properties of fasteners-Part2: Nuts, and thread |
20 | GB3098.3-2000 | Mechanical properties of fasteners-Part3: Fastening screw |
21 | GB/T5780-2000 | Helical Bolts Grade C |
22 | GB/T41-2000 | Helical Nuts Grade C |
23 | GB/T90-2002 | Flat Washer Grade C |
24 | GB/T13912-2002 | Metal Coating, Technical Requirement and Test Method for Hot-dip galvanized Metal Parts |
Standard | Description |
ASTM A6/A6M | Standard specification for general requirements for rolled structural steel bars, plates, and sheet piling. |
ASTM - 6 | - General Requirements for delivery of Rolled Steel Plates, Shapes, sheet Piling Bars for structural used |
ASTM A36/A36-M-97a | Standard specification for Carbon structural steel |
ASTM A123 / A123M-02 | Standard specification for Zinc (Hot-Dip Galvanized) Coatings on iron and steel products |
ASTM A143 / A143M-03 | Standard Practise for Safeguarding Against Embitterment of Hot-Dip Galvanized Structural Steel Products and Procedure for Detecting Embitterment |
ASTM A153/ A153M-05 | Standard specification for zinc coating (Hot-Dip) on iron and steel hardware |
ASTM A - 194 | - Grade for bolt |
ASTM A239 | Standard practice for locating the thinnest spot in a zinc (Galvanized) Coating on Iron or Steel Articles |
ASTM A242 | Standard specification for High-Strength Low-Alloy Structural steel |
ASTM A307 | Standard Specification for Carbon Steel Bolts and Studs, 60000 PSI Tensile strength |
ASTM A370-06 | Standard Test Methods and Definitions for Mechanical Testing of Steel Products |
ASTM A325 | Standard Specification for structural bolts, steel, Heat treated 120/105 ksi minimum tensile strength |
ASTM A-325 or A-354 | - Galvanized hexagonal head of connection bolt |
ASTM A325-97 | Standard Specification for High-strength Bolts for structural steel Joints |
ASTM A384 / A384M-02 | Standard Practise for Safeguarding Against Warpage and Distortion During Hot-Dip Galvanizing of Steel Assemblies. |
ASTM A394-93 | Standard Specification for steel Transmission Tower, Bolts, Zinc Coated and Bare |
ASTMA - 563 | - Class and size of nuts |
ASTMA - 572 | - Chemical composition of steel |
ASTM A572/A572-97c | Standard specification for High-Strength Low-Alloy Columbium-Vanadium Structural steel |
ASTMA - 615 | - The anchor bolt material |
ASTM A673 / A673M-07 | Standard Specification for Sampling Procedure for Impact Testing of Structural Steel |
ASTM B201 | Standard practice for testing Chromatic coating on Zinc and Cadmium surfaces |
ASTM E94-93 | Standard Guide for Radiographic Testing |
ASTM E 709-95 | Standard Guide for Magnetic Particle Examination |
ASCE Manual 72 | - Load testing a simple structure |
ASCE 10-97 | Standard Design of latticed steel transmission structures |
AWS D1.1 | American Welding Society D1,1/D1,1M structural Welding code- Steel |
ANSI B-182-2 | Bolts, nuts and washers dimensions |