Usage: | Crossing Tower, Tension Tower, Angle Tower, Terminal Tower, Transposition Tower, Branching Tower, 230kv DC and 500kv Sc Tangent Lattice Tower |
---|---|
Conductor Circuit: | Double Circuit |
Certification: | ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Temperature (ºC) | Wind speed (m/s) | Ice thickness (mm) |
Max. temperature | 40 | 0 | |
Mini. temperature | -20 | 0 | |
Ice thickness | -5 | 10 | 10 |
Basic wind speed | -5 | 25 | |
Installation condition | -10 | 10 | |
Annual temperature | 10 | ||
Lightning overvoltage | 15 | 10 | |
Operation overvoltage | 10 | 15 |
Item |
Conductor | OPGW | |
LGJ-150/25 | GJ-35 | ||
construction |
AL | 26/270 | |
Steel(Al wrap steel ) | 7/2.10 | 19×37/2.6.4 | |
Cross-section (mm2) |
Al | 173.11 | 37.17 |
Steel | 17.10 | 7.8 | |
Total | 0.601 | 0.295 | |
Diameter | 54110 | 43600 | |
Length mass (kg/km) | 0.1939 | 0.00.3 | |
Elastic module (MPa) | 76000 | 181423 | |
coefficient of linear expansion (1/ºC) | 18.9×10-6 | 11.5×10-6 |
Nominal Height |
12 | 15 | 18 | 21 | 24 | 27 | 30 |
tower weight Kg | 1488 | 1736 | 2175 | 2465 | 2920 | 3267 | 3743 |
Power voltage |
35KV |
Conductor type |
LGJ-150/25 | Max. operation Tension force (KN/phase) |
20562 |
Un-balance Stress value(%) |
50 |
OPGW Type |
GJ-35 | Max. operation Tension force (KN/pc) |
14210 |
Un-balance Stress value(%) |
50 |
Tower model | Nominal Height |
Horizontal span (m) |
Vertical Span (m) |
Representative Span (m) |
Angle º |
35B04-SZ1 | tower weight 3.734 ton | 300 | 450 | 1247 | 0 |
Site condition |
Normal operation condition | Accident condition | Installation condition |
||||||
Basic wind speed | Ice | Mini. temperature | Non-broken | broken | |||||
Climate condition (t/v/b) |
-5/25/0 | -5/10/10 | -20/0/0 | --/0/0 | --/0/0 | -10/10/0 | |||
Horizontal loading | conductor | 4231 | 1324 | ||||||
Insulator Power fitting | 100 | 16 | |||||||
Jump & string | |||||||||
OPGW | 1795 | 820 | |||||||
Vertical loading |
conductor | 4055 | 6062 | 4055 | 4055 | 304 | |||
Insulator Power fitting | 608 | 608 | 608 | 608 | 608 | 10812 | |||
Jump & string | |||||||||
OPGW | 1585 | 2733 | 1685 | 1685 | 4967 | ||||
Stress force | conductor | One side | |||||||
The other side | |||||||||
Stress differences | 10281 | ||||||||
OPGW | One side | ||||||||
The other side | |||||||||
Stress differences | 7105 | ||||||||
Nominal Height (m) |
Foundation distance (mm) | Anchor bolt | ||||
Front distance |
Side distance |
Front distance |
Side distance |
Material | ||
12 | 2441 | 2441 | 160 | 160 | M27 |
|
15 | 2781 | 2781 | 160 | 160 | ||
18 | 3111 | 3111 | 160 | 160 | ||
2 | 3446 | 3446 | 160 | 160 | ||
24 | 3778 | 3778 | 160 | 160 | ||
27 | 4108 | 4108 | 160 | 160 | ||
30 | 4438 | 4438 | 160 | 160 | ||
Nominal Height (m) |
Tx | Ty | T | Nx | Ny | N |
12 | 132.49 | 11.62 | 9.88 | 154.48 | 12.80 | 11.12 |
15 | 153.81 | 13.52 | 11.85 | 177.67 | 14.81 | 13.19 |
18 | 169.65 | 14.59 | 13.01 | 196.47 | 16.05 | 14.51 |
2 | 186.27 | 15.86 | 14.34 | 214.20 | 17.38 | 15.90 |
24 | 200.64 | 16.90 | 15.46 | 232.09 | 18.62 | 17.21 |
27 | 214.93 | 17.67 | 16.30 | 247.16 | 19.43 | 18.09 |
30 | 227.87 | 18.59 | 17.27 | 263.98 | 20.56 | 19.27 |
Steel material | Anti-push, bending and press strength (N/mm2) | Anti-shear strength (N/mm2) |
|
Grade | Thickness or diameter (mm) | ||
Q235 Steel |
≤16 | 215 | 125 |
>16~40 | 205 | 120 | |
>40~60 | 200 | 115 | |
>60~100 | 190 | 110 | |
Q345 Steel |
≤16 | 310 | 180 |
>16~35 | 295 | 170 | |
>35~50 | 265 | 155 | |
>50~100 | 250 | 145 | |
Q420 Steel |
≤16 | 380 | 220 |
>16~35 | 360 | 210 | |
>35~50 | 340 | 195 | |
>50~100 | 325 | 185 | |
Q460 Steel |
≤16 | 415 | 240 |
>16~35 | 395 | 230 | |
>35~50 | 380 | 220 | |
>50~100 | 360 | 210 |
Item | Grade | Anti-push strength (N/mm2) | Anti-shear strength (N/mm2) |
Fastener for towers |
4.8 | 200 | 170 |
5.8 | 240 | 210 | |
6.8 | 300 | 240 | |
8.8 | 400 | 300 | |
Anchor bolts |
Q235 | 160 | / |
Chinese 35 steel | 190 | / | |
Chinese 45 steel | 215 | / |
No | Code | DESCRIPTION |
1 | GB/T2694-2003 | Power Transmission line Steel tower - Technical requirements for manufacturing |
2 | JGJ81-2002 | Technical specification for welding for steel structure of building |
3 | GB9787-88 | Measuring and allowable tolerance for hot-rolled equal angle |
4 | GB709-88 | Measuring and allowable tolerance for hot-rolled plate and strip |
5 | GB/T699-1999 | Quality Carbon Structural Steel |
6 | GB/T1591-1994 | Low alloy high strength structural Steel |
7 | GB700-88 | Carbon Structural Steel |
8 | GB222-84 | Method of sampling steel for determination of chemical composition and permissible variations |
9 | GB/T228-2002 | Method for Tensile testing of metals |
10 | GB/T232-1999 | Method for Bending test of metals |
11 | GB/T5117-1995 | Carbon Welding Rod |
12 | GB/T5118-1995 | Low Alloy Welding Rod |
13 | GB/T8220-1995 | Welding wires for gas shielding arc welding of carbon and low alloy steels |
14 | GB/T10045-2001 | Carbon steel flux cored electrodes for arc welding |
15 | JB/T7949-1999 | Weld outer dimensions for steel construction |
16 | GB50205-2001 | Test Standard for Acceptance of Steel Structure |
17 | GB/T470-1997 | Zinc Ingot |
18 | GB3098.1-2000 | Mechanical properties of fasteners-Part 1:Bolts, screws and studs |
19 | GB3098.2-2000 | Mechanical properties of fasteners-Part2: Nuts, and thread |
20 | GB3098.3-2000 | Mechanical properties of fasteners-Part3: Fastening screw |
21 | GB/T5780-2000 | Helical Bolts Grade C |
22 | GB/T41-2000 | Helical Nuts Grade C |
23 | GB/T90-2002 | Flat Washer Grade C |
24 | GB/T13912-2002 | Metal Coating, Technical Requirement and Test Method for Hot-dip galvanized Metal Parts |
Standard | Description |
ASTM A6/A6M | Standard specification for general requirements for rolled structural steel bars, plates, and sheet piling. |
ASTM - 6 | - General Requirements for delivery of Rolled Steel Plates, Shapes, sheet Piling Bars for structural used |
ASTM A36/A36-M-97a | Standard specification for Carbon structural steel |
ASTM A123 / A123M-02 | Standard specification for Zinc (Hot-Dip Galvanized) Coatings on iron and steel products |
ASTM A143 / A143M-03 | Standard Practise for Safeguarding Against Embitterment of Hot-Dip Galvanized Structural Steel Products and Procedure for Detecting Embitterment |
ASTM A153/ A153M-05 | Standard specification for zinc coating (Hot-Dip) on iron and steel hardware |
ASTM A - 194 | - Grade for bolt |
ASTM A239 | Standard practice for locating the thinnest spot in a zinc (Galvanized) Coating on Iron or Steel Articles |
ASTM A242 | Standard specification for High-Strength Low-Alloy Structural steel |
ASTM A307 | Standard Specification for Carbon Steel Bolts and Studs, 60000 PSI Tensile strength |
ASTM A370-06 | Standard Test Methods and Definitions for Mechanical Testing of Steel Products |
ASTM A325 | Standard Specification for structural bolts, steel, Heat treated 120/105 ksi minimum tensile strength |
ASTM A-325 or A-354 | - Galvanized hexagonal head of connection bolt |
ASTM A325-97 | Standard Specification for High-strength Bolts for structural steel Joints |
ASTM A384 / A384M-02 | Standard Practise for Safeguarding Against Warpage and Distortion During Hot-Dip Galvanizing of Steel Assemblies. |
ASTM A394-93 | Standard Specification for steel Transmission Tower, Bolts, Zinc Coated and Bare |
ASTMA - 563 | - Class and size of nuts |
ASTMA - 572 | - Chemical composition of steel |
ASTM A572/A572-97c | Standard specification for High-Strength Low-Alloy Columbium-Vanadium Structural steel |
ASTMA - 615 | - The anchor bolt material |
ASTM A673 / A673M-07 | Standard Specification for Sampling Procedure for Impact Testing of Structural Steel |
ASTM B201 | Standard practice for testing Chromatic coating on Zinc and Cadmium surfaces |
ASTM E94-93 | Standard Guide for Radiographic Testing |
ASTM E 709-95 | Standard Guide for Magnetic Particle Examination |
ASCE Manual 72 | - Load testing a simple structure |
ASCE 10-97 | Standard Design of latticed steel transmission structures |
AWS D1.1 | American Welding Society D1,1/D1,1M structural Welding code- Steel |
ANSI B-182-2 | Bolts, nuts and washers dimensions |