Usage: | Tension Tower, Angle Tower, Terminal Tower, Transposition Tower, Branching Tower, According to Client′s Technical Specification |
---|---|
Conductor Circuit: | Single Circuit |
Certification: | ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Mainly Meteorological Data | ||||
Design Meteorological | Temperature (˚C) | Wind Velocity (m/s) | ||
Conditions | ||||
Max.Ambient Temperature | 40 | 0 | ||
Everyday Temperature | 30 | 0 | ||
Min. Temperature | 10 | 0 | ||
Max. wind | - | 34 at 44˚C | ||
Installing Condition | 44 | 10 | ||
Max. Conductor Temperature | 74 | 0 |
Type | ACSR Conductor (604 MCM, Duck) |
Earth Wire (GJ-40) |
||
Structure (no./mm) | Aluminum | 44/4.68 | ||
Steel | 7/4.68 | 18/1.8 | ||
Outside Diameter | 44.41 | 8 | ||
Sectional Area (mm4) | Aluminum | 306.8 | ||
Steel | 38.78 | 40 | ||
Overall Section Area (mm4) | 346.68 | 40 | ||
Unit Weight (kg/km) | 1.148 | 0.384 | ||
Ultimate Strength (kN) | 101.6 | 48 | ||
Comprehensive Elastic Factor (N/mm4) | 70000 | 181300 | ||
Comprehensive Expansion Factor (1/C x 10E -6) | 18.3 | 11.4 | ||
40˚C Direct Current Resistance | 0.08443 | |||
Breaking Stress (N/mm4) | 478 | 1170 | ||
Actual Max. Stress (N/mm4) | 106 | 488 | ||
Everyday Operation Stress (N/mm4) | 61 | 180 | ||
Normalization | CSA-C48-1864 | GB1400-88 |