Usage: | Crossing Tower, Tension Tower, Angle Tower, Terminal Tower, Transposition Tower, Branching Tower, According to Client Requirements |
---|---|
Conductor Circuit: | Double Circuit |
Certification: | ISO, GS |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Temperature (ºC) | Wind speed (m/s) | Ice thickness (mm) |
Max. temperature | 40 | 0 | 0 |
Mini. temperature | -15 | 0 | 0 |
Ice thickness | -5 | 10 | 10 |
Basic wind speed | -5 | 30 | 0 |
Installation condition | -5 | 10 | 0 |
Annual temperature | 15 | 10 | 0 |
Lightning overvoltage | 15 | 15 | 0 |
Operation overvoltage | 15 | 18 | 0 |
Item |
Conductor | OPGW | |
JL/G1A-630/45 | JLB20A-240 | ||
construction |
AL | 45×3.76 | 59.69 |
Steel(Al wrap steel ) | 45×4.22 | 179.07 | |
Cross-section (mm2) |
Al | 630.00 | 238.76 |
Steel | 43.39 | 20.01 | |
Total | 674.00 | 1595.50 | |
Diameter | 33.80 | 147200 | |
Length mass (kg/km) | 2079.20 | 13.0×10-6 | |
Elastic module (MPa) | 63000 | 147200 | |
coefficient of linear expansion (1/ºC) | 20.9×10-6 | 13.0×10-6 | |
Rated broken (N) | 150450 | 260010 |
Tower type |
Nominal Height (mm) |
Horizontal span (m) |
Vertical Span (m) |
Angle º |
Nominal height tower weight Kg |
10GB2-SZ1 | 54 | 400 | 500 | 0 | 111569 |
Power voltage |
1000KV |
Conductor type |
8×JL/ GIA-630/45 |
Max. operation Tension force (KN/phase) |
457.368 |
Un-balance Stress value(%) |
10 |
OPGW Type |
JLB20A-240 | Max. operation Tension force (KN/pc) |
68.424 | Un-balance Stress value(%) |
20 |
Item |
Horizontal span (m) |
Vertical Span (m) |
Representative Span (m) |
Angle º |
Height (m) |
KV |
data | 400 | 500 | 400 | 0 | 54 | 0.85 |
Site condition |
Normal operation condition | Accident condition | Installation condition |
Uneven icing | |||||
Basic wind speed | Ice | Mini. temperature |
Non- broken |
broken | |||||
Climate condition (t/v/b) |
-5/30/0 | -5/10/10 | -40/0/0 | -5/0/10 | -5/0/10 | -15/10/0 | -5/10/10 | ||
Horizontal loading | conductor | 92441 | 20081 | - | - | - | 9638 | 20081- | |
Insulator Power fitting |
8640 | 1440 | - | - | - | 1440 | 1440- | ||
OPGW | 9051 | 2253 | - | - | - | 861 | 2253- | ||
conductor | 81560 | 130160 | 81560 | 130160 | 130160 | 81560 | 130160- | ||
Vertical loading |
Insulator Power fitting |
||||||||
OPGW | 7825 | 11985 | 7825 | 11985 | 11985 | 7825 | 119825- | ||
Stress force | conductor | One side | - | -- | - | 91474 | 91474 | - | -- |
The other side | - | -- | - | 91474 | 0 | - | -- | ||
Stress differences | - | -- | -- | 0 | 91474 | - | 45737 | ||
Stress force | OPGW OPGW |
One side | - | -- | 68424 | 68424 | - | -- | |
The other side | - | -- | 68424 | 0 | - | -- | |||
Stress differences | - | -- | 0 | 68424 | - | 13685 |
Nominal Height (m) |
Foundation distance (mm) | Anchor bolt | |||
Front distance |
Side distance |
Type and quantity | Distance /radius (mm) | Material | |
45 | 15860 | 15860 | 12×M52 |
396 | Chinese type 35 steel |
48 | 16532 | 16532 | |||
51 | 17204 | 17204 | 410 | ||
54 | 17876 | 17876 | |||
57 | 18548 | 18548 | 420.5 | ||
60 | 19220 | 19220 |
Nominal Height (m) |
Tx | Ty | T | Nx | Ny | N |
45 | 338 | 313 | 2655 | 436 | 409 | 3492 |
48 | 346 | 325 | 2719 | 449 | 426 | 3577 |
51 | 353 | 332 | 2765 | 459 | 436 | 3647 |
54 | 365 | 338 | 2803 | 457 | 442 | 3728 |
57 | 371 | 343 | 2846 | 475 | 450 | 3795 |
60 | 379 | 359 | 2894 | 494 | 475 | 3865 |
Steel material | Anti-push, bending and press strength (N/mm2) | Anti-shear strength (N/mm2) |
|
Grade | Thickness or diameter (mm) | ||
Q235 Steel |
≤16 | 215 | 125 |
>16~40 | 205 | 120 | |
>40~60 | 200 | 115 | |
>60~100 | 190 | 110 | |
Q345 Steel |
≤16 | 310 | 180 |
>16~35 | 295 | 170 | |
>35~50 | 265 | 155 | |
>50~100 | 250 | 145 | |
Q420 Steel |
≤16 | 380 | 220 |
>16~35 | 360 | 210 | |
>35~50 | 340 | 195 | |
>50~100 | 325 | 185 | |
Q460 Steel |
≤16 | 415 | 240 |
>16~35 | 395 | 230 | |
>35~50 | 380 | 220 | |
>50~100 | 360 | 210 |
Item | Grade | Anti-push strength (N/mm2) | Anti-shear strength (N/mm2) |
Fastener for towers |
4.8 | 200 | 170 |
5.8 | 240 | 210 | |
6.8 | 300 | 240 | |
8.8 | 400 | 300 | |
Anchor bolts |
Q235 | 160 | / |
Chinese 35 steel | 190 | / | |
Chinese 45 steel | 215 | / |
No | Code | DESCRIPTION |
1 | GB/T2694-2003 | Power Transmission line Steel tower - Technical requirements for manufacturing |
2 | JGJ81-2002 | Technical specification for welding for steel structure of building |
3 | GB9787-88 | Measuring and allowable tolerance for hot-rolled equal angle |
4 | GB709-88 | Measuring and allowable tolerance for hot-rolled plate and strip |
5 | GB/T699-1999 | Quality Carbon Structural Steel |
6 | GB/T1591-1994 | Low alloy high strength structural Steel |
7 | GB700-88 | Carbon Structural Steel |
8 | GB222-84 | Method of sampling steel for determination of chemical composition and permissible variations |
9 | GB/T228-2002 | Method for Tensile testing of metals |
10 | GB/T232-1999 | Method for Bending test of metals |
11 | GB/T5117-1995 | Carbon Welding Rod |
12 | GB/T5118-1995 | Low Alloy Welding Rod |
13 | GB/T8220-1995 | Welding wires for gas shielding arc welding of carbon and low alloy steels |
14 | GB/T10045-2001 | Carbon steel flux cored electrodes for arc welding |
15 | JB/T7949-1999 | Weld outer dimensions for steel construction |
16 | GB50205-2001 | Test Standard for Acceptance of Steel Structure |
17 | GB/T470-1997 | Zinc Ingot |
18 | GB3098.1-2000 | Mechanical properties of fasteners-Part 1:Bolts, screws and studs |
19 | GB3098.2-2000 | Mechanical properties of fasteners-Part2: Nuts, and thread |
20 | GB3098.3-2000 | Mechanical properties of fasteners-Part3: Fastening screw |
21 | GB/T5780-2000 | Helical Bolts Grade C |
22 | GB/T41-2000 | Helical Nuts Grade C |
23 | GB/T90-2002 | Flat Washer Grade C |
24 | GB/T13912-2002 | Metal Coating, Technical Requirement and Test Method for Hot-dip galvanized Metal Parts |
Standard | Description |
ASTM A6/A6M | Standard specification for general requirements for rolled structural steel bars, plates, and sheet piling. |
ASTM - 6 | - General Requirements for delivery of Rolled Steel Plates, Shapes, sheet Piling Bars for structural used |
ASTM A36/A36-M-97a | Standard specification for Carbon structural steel |
ASTM A123 / A123M-02 | Standard specification for Zinc (Hot-Dip Galvanized) Coatings on iron and steel products |
ASTM A143 / A143M-03 | Standard Practise for Safeguarding Against Embitterment of Hot-Dip Galvanized Structural Steel Products and Procedure for Detecting Embitterment |
ASTM A153/ A153M-05 | Standard specification for zinc coating (Hot-Dip) on iron and steel hardware |
ASTM A - 194 | - Grade for bolt |
ASTM A239 | Standard practice for locating the thinnest spot in a zinc (Galvanized) Coating on Iron or Steel Articles |
ASTM A242 | Standard specification for High-Strength Low-Alloy Structural steel |
ASTM A307 | Standard Specification for Carbon Steel Bolts and Studs, 60000 PSI Tensile strength |
ASTM A370-06 | Standard Test Methods and Definitions for Mechanical Testing of Steel Products |
ASTM A325 | Standard Specification for structural bolts, steel, Heat treated 120/105 ksi minimum tensile strength |
ASTM A-325 or A-354 | - Galvanized hexagonal head of connection bolt |
ASTM A325-97 | Standard Specification for High-strength Bolts for structural steel Joints |
ASTM A384 / A384M-02 | Standard Practise for Safeguarding Against Warpage and Distortion During Hot-Dip Galvanizing of Steel Assemblies. |
ASTM A394-93 | Standard Specification for steel Transmission Tower, Bolts, Zinc Coated and Bare |
ASTMA - 563 | - Class and size of nuts |
ASTMA - 572 | - Chemical composition of steel |
ASTM A572/A572-97c | Standard specification for High-Strength Low-Alloy Columbium-Vanadium Structural steel |
ASTMA - 615 | - The anchor bolt material |
ASTM A673 / A673M-07 | Standard Specification for Sampling Procedure for Impact Testing of Structural Steel |
ASTM B201 | Standard practice for testing Chromatic coating on Zinc and Cadmium surfaces |
ASTM E94-93 | Standard Guide for Radiographic Testing |
ASTM E 709-95 | Standard Guide for Magnetic Particle Examination |
ASCE Manual 72 | - Load testing a simple structure |
ASCE 10-97 | Standard Design of latticed steel transmission structures |
AWS D1.1 | American Welding Society D1,1/D1,1M structural Welding code- Steel |
ANSI B-182-2 | Bolts, nuts and washers dimensions |