Usage: | Crossing Tower, Tension Tower, Angle Tower, Terminal Tower, Transposition Tower, Branching Tower, According to Client Desing or Requirement |
---|---|
Conductor Circuit: | Double Circuit |
Certification: | ISO |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item | Temperature (ºC) | Wind speed (m/s) | Ice thickness (mm) |
Max. temperature | 40 | 0 | 0 |
Mini. temperature | -30 | 0 | 0 |
Ice thickness | -5 | 10 | 10 |
Basic wind speed | -5 | 27 | 0 |
Installation condition | -15 | 10 | 0 |
Annual temperature | 10 | 0 | 0 |
Lightning overvoltage | 15 | 10 | 0 |
Operation overvoltage | 10 | 15 | 0 |
Item |
Conductor | OPGW | |
JL/G1A-400/50 | JLB20A-150 | ||
construction | AL | 54×3.07 | -- |
Steel(Al wrap steel ) | 7×3.07 | 19×3.15 | |
Cross-section (mm2) |
451.55 | 148.07 | |
Diameter | 27.63 | 15.75 | |
Length mass (kg/km) | 1.511 | 0.990 | |
Elastic module (MPa) | 123400 | 178570 | |
coefficient of linear expansion (1/ºC) | 20.9×10-6 | 13.0×10-6 |
Tower type |
Nominal Height Scope (mm) |
Horizontal span (m) |
Vertical Span (m) |
Angle º |
Nominal height tower weight Kg |
7C1-SZ3 | 51 | 670 | 900 | 0~3 | 98759 |
Power voltage |
750KV |
Conductor type |
6×JL/ G3A-900/40 |
Max. operation Tension force (KN/phase) |
463.729 | Un-balance Stress value(%) |
10 |
OPGW Type |
JLB20A-150 | Max. operation Tension force (KN/pc) |
59.523 | Un-balance Stress value(%) |
20 |
Item | Horizontal span (m) |
Vertical Span (m) |
Representative Span (m) |
Angle º |
Height (m) |
KV |
data | 800 | 1000 | 400 | 0~2 | 57 | 0.65 |
Site condition |
Normal operation condition | Accident condition | Installation condition |
Non-uniform Ice condition |
||||||
Basic wind speed | Ice | Mini. temperature |
Non- broken |
broken | ||||||
Climate condition (t/v/b) |
-5/27/0 | -5/10/10 | -30/0/0 | -5/0/10 | -5/0/10 | 15/0/0 | -5/10/10 | |||
Horizontal loading | conductor | 70662 | 17984 | 0 | 0 | 0 | 8319 | 17984 | ||
Insulator Power fitting |
3236 | 431 | 0 | 0 | 0 | 359 | 431 | |||
OPGW | 11391 | 4568 | 0 | 0 | 0 | 1234 | 4568 | |||
Vertical loading |
conductor | 84877 | 140670 | 87719 | 140988 | 140860 | 145373 | 126479 | ||
Insulator Power fitting |
20000 | 21803 | 20000 | 21803 | 21803 | 33000 | 21803 | |||
OPGW | 8799 | 19561 | 9275 | 19605 | 11763 | 20283 | 16780 | |||
Climate condition (t/v/b) |
-5/27/0 | -5/10/10 | -30/0/0 | -5/0/10 | -5/0/10 | 15/0/0 | -5/10/10 | |||
Stress force | conductor | One side | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
The other side | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |||
Stress differences | 0 | 0 | 0 | 0 | 0 | 56270 | 0 | |||
OPGW | One side | 0 | 0 | 0 | 0 | 0 | 0 | 10204 | ||
The other side | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |||
Stress differences | 0 | 0 | 0 | 0 | 0 | 51020 | 0 | |||
Nominal Height (m) |
Foundation distance (mm) | Anchor bolt | |||
Front distance |
Side distance |
Type and quantity | Distance /radius (mm) | Material | |
36 | 14142 | 4×M64 | 370 | Chinese type 8*M56 |
|
39 | 14863 | ||||
42 | 15583 | ||||
45 | 16303 | ||||
48 | 17023 | ||||
51 | 17743 | ||||
54 | 18464 | 370 | 370 | ||
57 | 19184 | ||||
60 | 19904 |
Nominal Height (m) |
Tx | Ty | T | Nx | Ny | N |
36 | 2027 | 292 | 270 | 2608 | 369 | 335 |
39 | 2056 | 293 | 273 | 2638 | 370 | 337 |
42 | 2084 | 294 | 275 | 2665 | 371 | 339 |
45 | 2101 | 303 | 281 | 2717 | 383 | 349 |
48 | 2129 | 304 | 283 | 2744 | 384 | 352 |
51 | 2256 | 335 | 308 | 2915 | 420 | 381 |
54 | 2288 | 337 | 310 | 2946 | 421 | 384 |
57 | 2318 | 338 | 312 | 2976 | 422 | 387 |
60 | 2346 | 339 | 315 | 3004 | 423 | 389 |
Steel material | Anti-push, bending and press strength (N/mm2) | Anti-shear strength (N/mm2) |
|
Grade | Thickness or diameter (mm) | ||
Q235 Steel |
≤16 | 215 | 125 |
>16~40 | 205 | 120 | |
>40~60 | 200 | 115 | |
>60~100 | 190 | 110 | |
Q345 Steel |
≤16 | 310 | 180 |
>16~35 | 295 | 170 | |
>35~50 | 265 | 155 | |
>50~100 | 250 | 145 | |
Q420 Steel |
≤16 | 380 | 220 |
>16~35 | 360 | 210 | |
>35~50 | 340 | 195 | |
>50~100 | 325 | 185 | |
Q460 Steel |
≤16 | 415 | 240 |
>16~35 | 395 | 230 | |
>35~50 | 380 | 220 | |
>50~100 | 360 | 210 |
Item | Grade | Anti-push strength (N/mm2) | Anti-shear strength (N/mm2) |
Fastener for towers |
4.8 | 200 | 170 |
5.8 | 240 | 210 | |
6.8 | 300 | 240 | |
8.8 | 400 | 300 | |
Anchor bolts |
Q235 | 160 | / |
Chinese 35 steel | 190 | / | |
Chinese 45 steel | 215 | / |
No | Code | DESCRIPTION |
1 | GB/T2694-2003 | Power Transmission line Steel tower - Technical requirements for manufacturing |
2 | JGJ81-2002 | Technical specification for welding for steel structure of building |
3 | GB9787-88 | Measuring and allowable tolerance for hot-rolled equal angle |
4 | GB709-88 | Measuring and allowable tolerance for hot-rolled plate and strip |
5 | GB/T699-1999 | Quality Carbon Structural Steel |
6 | GB/T1591-1994 | Low alloy high strength structural Steel |
7 | GB700-88 | Carbon Structural Steel |
8 | GB222-84 | Method of sampling steel for determination of chemical composition and permissible variations |
9 | GB/T228-2002 | Method for Tensile testing of metals |
10 | GB/T232-1999 | Method for Bending test of metals |
11 | GB/T5117-1995 | Carbon Welding Rod |
12 | GB/T5118-1995 | Low Alloy Welding Rod |
13 | GB/T8220-1995 | Welding wires for gas shielding arc welding of carbon and low alloy steels |
14 | GB/T10045-2001 | Carbon steel flux cored electrodes for arc welding |
15 | JB/T7949-1999 | Weld outer dimensions for steel construction |
16 | GB50205-2001 | Test Standard for Acceptance of Steel Structure |
17 | GB/T470-1997 | Zinc Ingot |
18 | GB3098.1-2000 | Mechanical properties of fasteners-Part 1:Bolts, screws and studs |
19 | GB3098.2-2000 | Mechanical properties of fasteners-Part2: Nuts, and thread |
20 | GB3098.3-2000 | Mechanical properties of fasteners-Part3: Fastening screw |
21 | GB/T5780-2000 | Helical Bolts Grade C |
22 | GB/T41-2000 | Helical Nuts Grade C |
23 | GB/T90-2002 | Flat Washer Grade C |
24 | GB/T13912-2002 | Metal Coating, Technical Requirement and Test Method for Hot-dip galvanized Metal Parts |
Standard | Description |
ASTM A6/A6M | Standard specification for general requirements for rolled structural steel bars, plates, and sheet piling. |
ASTM - 6 | - General Requirements for delivery of Rolled Steel Plates, Shapes, sheet Piling Bars for structural used |
ASTM A36/A36-M-97a | Standard specification for Carbon structural steel |
ASTM A123 / A123M-02 | Standard specification for Zinc (Hot-Dip Galvanized) Coatings on iron and steel products |
ASTM A143 / A143M-03 | Standard Practise for Safeguarding Against Embitterment of Hot-Dip Galvanized Structural Steel Products and Procedure for Detecting Embitterment |
ASTM A153/ A153M-05 | Standard specification for zinc coating (Hot-Dip) on iron and steel hardware |
ASTM A - 194 | - Grade for bolt |
ASTM A239 | Standard practice for locating the thinnest spot in a zinc (Galvanized) Coating on Iron or Steel Articles |
ASTM A242 | Standard specification for High-Strength Low-Alloy Structural steel |
ASTM A307 | Standard Specification for Carbon Steel Bolts and Studs, 60000 PSI Tensile strength |
ASTM A370-06 | Standard Test Methods and Definitions for Mechanical Testing of Steel Products |
ASTM A325 | Standard Specification for structural bolts, steel, Heat treated 120/105 ksi minimum tensile strength |
ASTM A-325 or A-354 | - Galvanized hexagonal head of connection bolt |
ASTM A325-97 | Standard Specification for High-strength Bolts for structural steel Joints |
ASTM A384 / A384M-02 | Standard Practise for Safeguarding Against Warpage and Distortion During Hot-Dip Galvanizing of Steel Assemblies. |
ASTM A394-93 | Standard Specification for steel Transmission Tower, Bolts, Zinc Coated and Bare |
ASTMA - 563 | - Class and size of nuts |
ASTMA - 572 | - Chemical composition of steel |
ASTM A572/A572-97c | Standard specification for High-Strength Low-Alloy Columbium-Vanadium Structural steel |
ASTMA - 615 | - The anchor bolt material |
ASTM A673 / A673M-07 | Standard Specification for Sampling Procedure for Impact Testing of Structural Steel |
ASTM B201 | Standard practice for testing Chromatic coating on Zinc and Cadmium surfaces |
ASTM E94-93 | Standard Guide for Radiographic Testing |
ASTM E 709-95 | Standard Guide for Magnetic Particle Examination |
ASCE Manual 72 | - Load testing a simple structure |
ASCE 10-97 | Standard Design of latticed steel transmission structures |
AWS D1.1 | American Welding Society D1,1/D1,1M structural Welding code- Steel |
ANSI B-182-2 | Bolts, nuts and washers dimensions |